Electrical Specifications |
|
|
Input value of the METEC-30K(DC side) |
|
|
DC Input voltage range |
380V-650V |
|
Start-up DC Voltage |
380V |
|
Rated power DC Voltage Point |
540V |
|
DC Voltage Ripple |
VPP < 10 % |
|
Personnel Protection |
Ground |
|
Output value of the METEC-30K(grid side) |
|
|
Nominal AC output power |
30KW |
|
Continuous over-load capacity |
110% (of nominal power) |
|
Allowable Grid Voltage Range (line- to-line voltage ) |
310V – 450 V AC |
|
Allowable grid Frequency Range |
49-51/59-61Hz |
|
Power Factor |
>0.99 |
|
Peak Efficiency |
94 % |
|
European Efficiency |
93.5 % |
|
Internal consumption during operation |
<100w |
|
Internal consumption during stand-by |
<10 W |
|
Protection |
Short circuit protection Islanding Protection Over Load Protection |
|
Total Current Harmonic Distortion (THD) |
THD< 3 % |
|
Phase Shift |
0 |
|
Utility Monitoring |
in accordance with UL 1741
|
|
Mechanical Specifications
|
|
|
Inverter Dimensions(W x H x D) |
800x 1800 x600 mm |
|
Unit Weight |
500kg |
|
Waterproof Class |
IP20 |
|
Mounting |
Placed on the floor |
|
Operating Temperature Range |
-20°C - 40°C |
|
Features
|
|
|
Utility Disconnect |
Complies with NEC |
|
Cooling |
FAN |
|
Display |
LEDs and LCD |
|
Communication |
RS485 |
|
EMC |
EN50081, part1 EN50082, part1 |
|
Safety |
EN 50178 |
|
Grid interference |
EN61000-3-2 |